Key points
- A transfer structure is needed when the tower column grid differs from the grid of the podium and basement.
- Common types are transfer beams, transfer slabs and transfer trusses.
- SNI 1726:2019 treats offsets in seismic elements as Type 4 irregularities with extra design requirements.
- Storey height, cost and long-term deflection should be agreed with the architect at concept stage.

Many city buildings stack two uses in one block: a mall or plaza at the bottom, with a hotel or apartments above. The trouble is that the column grid that suits open retail floors rarely matches the grid that suits hotel rooms. Where the two meet, engineers often use transfer structures: elements that carry the load of columns or walls above across to columns below that sit in different positions.
Why the column grid changes between podium and tower
Each use has its own space needs:
- Hotel rooms and apartments work well with fairly close column spacing and walls that repeat on every floor. The walls between rooms are often used as structural walls.
- Malls, lobbies and ballrooms need wide open space, free of columns that get in the way of shoppers, shop fronts or table layouts.
- Basement car parks follow their own logic: the grid follows the size of driving aisles and parking bays.
When all three are stacked in one building, the tower columns cannot simply run straight down to the foundation without spoiling the floors below. That is where a transfer level comes in.
Common types of transfer structure
There are several ways to carry load from a column or wall that stops to the supports below:
| Type | How it works | Notes |
|---|---|---|
| Transfer beam | A deep beam picks up a column and passes the load to two supporting columns | Most common; its depth can eat into storey height |
| Transfer slab | A thick concrete slab picks up many columns and walls at once | Flexible for very different grids, but very heavy |
| Transfer truss | A storey-deep truss acts as a giant beam | The truss storey can often house plant rooms |
The right choice depends on the loads, how far columns must shift, the available storey height and the construction method. For large transfer beams or slabs, prestressing is sometimes considered to control deflection; see our article on post-tensioned slabs.
Transfer structures and seismic irregularity
A transfer structure is not only about gravity loads. In an earthquake, lateral forces from the walls or frames above must also find a path to the foundation. SNI 1726:2019 treats these conditions as structural irregularities, including:
- Horizontal irregularity Type 4, out-of-plane offset: a lateral-force-resisting element steps out of its own plane at a lower level.
- Vertical irregularity Type 4, in-plane discontinuity in the vertical lateral-force-resisting elements: for example, a shear wall that shifts position within its own plane.
For structures in seismic design category D, E or F with these irregularities, SNI 1726:2019 clause 7.3.3.4 requires the design forces for diaphragm connections and collectors to be increased by 25%, except where forces already include the overstrength factor (Ω0). The American standard ASCE 7-16 also requires elements that support discontinuous walls or frames to be designed with load combinations that include overstrength. In practice, transfer beams and their supporting columns are designed stronger than ordinary members, because their failure could affect the whole building above.
Tip: Where the architecture allows, keep shear walls and lift cores running straight down to the foundation. Use transfer structures for the columns that really must move, not for the whole seismic system.
What owners and architects should watch
A transfer structure affects more than the structural drawings:
- Storey height. Transfer beams or slabs can be very deep, so space for ducts, sprinklers and ceilings must be planned together from the start.
- Cost and time. Transfer elements need large volumes of concrete and reinforcement, strong formwork and propping, and a planned pour sequence.
- Long-term deflection. Creep and shrinkage make deflection grow over time. This must be allowed for so that walls and facades above do not crack.
- Later changes. Adding storeys or changing use above a transfer level must be checked by an engineer, because transfer elements are a critical load path.
The size of a transfer element always comes from the calculation for a specific project. This article explains the concept, not dimensions to copy.
Building type example: hotel and plaza in one project
Tangram Hotel & Sadira Plaza in Pekanbaru combines a hotel and a plaza in one development. Stadin's project data records it as 15 storeys with 2 basements, 2 towers, a floor area of 28,000 m², bored pile foundations and the year 2013. In this type of building, the meeting point of retail grids, hotel rooms and basement parking is one of the structural decisions to settle at concept stage. You can see Stadin's other hotel work on the hotels sector page.
Conclusion
Transfer structures let one building hold different uses above and below. The price is heavy members, stricter seismic design and closer coordination between the architect, MEP engineer and structural engineer. The earlier the need for a transfer is discussed, the better the chance of an efficient solution.
If you are planning a mixed-use building, our structural design team can help.
This article provides general information. Every project still needs to be analysed and calculated by a competent structural or geotechnical engineer, in line with the applicable SNI codes and regulations.